Leoch 12V 240.8Ah XP Series UPS High Rate Battery
- SKU: XP12-210FR
$271.15
- Manufacturer: Leoch
- Data Sheet: Download
Product Information
12V 240.8Ah XP Series UPS High Rate Battery
The XP series batteries utilize advanced VRLA & TTP technology and are specifically designed for UPS and power supply applications, achieving a design life of 12 years at an ambient temperature of 25°C. By employing high-strength grids and special paste plates, they ensure excellent durability and stable performance even under high-rate discharge conditions.
Applications:
- Critical UPS (High rate) applications
- High power backup supply
- Emergency power supply
- Emergency lighting
- Electric starting
Compliant Standards:
- High Performance (10~12 years design life)
IEC60896-21/22:2004
BS 6290 Part 4
Specifications
Specifications XP12-210FR
| Rated Voltage | 12V |
| Nominal Capacity(8 HR) | 51.6 Ah at 1.75V/cell @ 25 C/77 F |
| Watts(15 min rate) | 225.1 Watts/cell at 1.67V/cell @ 25 C/77 F |
| Dimension | 9.02" x 5.43" x 7.87" inch |
| Total Height (with Terminal) | 203mm(7.99 inches) |
| Weight | Approx 17.3 kg (38.1lbs) |
| Terminal | T6 with copper alloy insert for a M6 bolt |
| Container Material | Flame Retardant ABS to UL94-V0 |
| Rated Capacity | 55.0 AH/2.75A (20hr,1.80V/cell,25 C/77 F) 51.6 AH/6.45A (8hr,1.75V/cell,25 C/77 F) 47.4 AH/9.47A (5hr,1.75V/cell,25 C/77 F) 43.8 AH/14.6A (3hr,1.75V/cell,25 C/77 F) 38.9 AH/38.9A (1hr,1.60V/cell,25 C/77 F) |
| Max. Discharge Current | 825A (5s) |
| Internal Resistance | Approx 5.0mΩ |
| Operating Temp. Range | Discharge -20~50℃ (4~131°F) Charge -0~50℃ (-32~122°F) Storage -20~55℃ (4~131°F) |
| Nominal Operating Temp. Range | 20 to 25 C (68 to 77 F ) |
| Cycle Use | Initial Charging Current less than 16.5A. 0 0 0 14.4V~15.0V at 25 C (77 F) Temp. Coefficient -30mV/ C |
| Standby Use | No limit on Initial Charging Current. 0 0 0 13.5V~13.8V at 25 C (77 F) Temp. Coefficient -20mV/ C |
| Capacity affected by Temperature | 40℃ (104°F) : 103% 25℃ (77°F) : 100% 0℃ (32°F) : 86% |
| Self Discharge | ≤ 0 3% of capacity declined per month at 25 C |